Technical Data
Working Voltage: AC220V±10% 50HZ
Backup Battery: DC24V (2 batteries DC12V in series, Capacity:17AH)
Rated power consumption: 864W
Controlled output: Double group interlocking output DC27V
Working Temperature R: -10℃-+75℃
Relative Humidity: ≦95%(40±2℃)
Box Size: 600 mm×500 mm×200 mm(H×W×D)
Weight: 30kg
The battery ‘s continuous operating time under full load status: 15 Minutes
And the standby time of battery is 72 hours after power off.
Output Control way:
1,Manual control output:Open/close window by manual button
2, Automatic control output:Manual button/Fire linkage control/
Emergency button trigger/ multiple smart control option
The range of control panel we supplied:
1 |
Control output
|
16A |
32A |
48A |
64A |
2 |
Battery( insertable )
|
12Ah |
17Ah |
24Ah |
38Ah |
Basic Function
1、 Our control panel with manual and automatic control way, Press the button of open/close/stop to control the window via
the manual button on the panel by manual Under automatic control status,
it can receive the fire signal from fire center to open all window in the firing route Meanwhile it
will give the alarm and send passive signal to fire center.
2, There is emergency button connected to the panel and our panel can
receive the triggered signal to open all windows in this firing route and
sounds alarm,meanwhile send passive signal to fire center.
3、 There is manual natural ventilation button for option,it can control all windows
by manual ( open/stop/close) for natural ventilation without any fire/emergency signal
received from the control panel.
4、 There is wind&rain sensor for option, it can close all windows after receive the signal
from W/R sensor when there is rainfall and storm coming.